Electrical Wiring Regulations, 2012 (L.I. 2008)

Regulation 2 Application
(1) These Regulations apply to
(a) electrical installations where the nominal voltages do not exceed
(i) 1000 Volts a.c. and 1500 Volts d.c. between conductors
(ii) 600 Volts a.c and 900 Volts d.c. between conductors and earth and
(iii) 50 Volts a.c or 120 Volts ripple free d.c whether between conductors or to earth; and

(b) an overhead interconnection between two or more buildings on the same premises.

(2) These Regulations do not apply to
(a) an overhead distribution installation located outside the premises 
(b) the internal wiring of a manufactured apparatus which is not wired on site
(c) a part of or the whole of a telecommunication appliance, fire alarm, emergency lighting circuit or electrical equipment which is not fed directly from an electrical distribution network; or
(d) an installation in a mine, quarry, mobile offshore facility and fixed offshore facility which is provided for under an enactment.